DCS跳线, LCDU/PC - LCDU/APC, E9/125 G.652.D BLO

高性能

DCS跳线(FR/LSZH),2根OS2光纤

产品型号和库存

产品编号 库存 产品长度 (m)极性Weight [kg]包装单位GTIN / EAN
47339000ZY
DCS patch cable LCDU/PC - LCDU/APC1A to A0.02 kg1 个40393910007206
47339100ZY
DCS patch cable LCDU/PC - LCDU/APC2A to A0.02 kg1 个40393910007190
47339200ZY
DCS patch cable LCDU/PC - LCDU/APC3A to A0.03 kg1 个40393910007183
47339300ZY
DCS patch cable LCDU/PC - LCDU/APC4A to A0.03 kg1 个40393910007176
47339400ZY
DCS patch cable LCDU/PC - LCDU/APC5A to A0.04 kg1 个40393910007169
47338000ZY
DCS patch cable LCDU/PC - LCDU/APC1A to B0.02 kg1 个40393910007268
47338100ZY
DCS patch cable LCDU/PC - LCDU/APC2A to B0.02 kg1 个40393910007251
47338200ZY
DCS patch cable LCDU/PC - LCDU/APC3A to B0.03 kg1 个40393910007244
47338300ZY
DCS patch cable LCDU/PC - LCDU/APC4A to B0.03 kg1 个40393910007237
47338400ZY
DCS patch cable LCDU/PC - LCDU/APC5A to B0.04 kg1 个40393910007220

技术规格书

其他长度请咨询
每根跳线都带推拉杆
具有Intelli-Cross® 性能的Uniboot跳线,可快速改变极性
紧凑型线缆设计,FR/LS0H护套(2.1 mm) , 2 芯
标准长度可达10m.
连接方式 A 至 A 或 A至B.
两端带标签
供货范围 带有LCD Uniboot Intelli-Cross Pro的高性能连接器组件。
所有连接器有推拉杆
DCS跳线(FR/LSZH),2根OS2光纤
两端带标签条
注意 连接方式根据TIA-568-C.3及EN 50174-1:2009
圆跳线的两端都装有LCD Uniboot Intelli-Cross Pro 连接器(高性能)。
LCD到LCD跳线适用于数据中心环境中具有双工信号的所有高性能应用。
跳线的组装质量很高,可以保证光学性能(IL / RL)达到最佳值。
电缆 围绕
外护套 FR/LSZH
外护套颜色 黄色
烟密度 IEC 61034-1/-2
零卤素无腐蚀性气体 IEC 60754-1/-2
火焰传播 IEC 60332-1-2
火焰蔓延 IEC 60332-3-22
连接器类型 A端 LCDU/PC
连接器端面 A PC 0°
连接器 A外壳颜色 蓝色
Release mechanism side A Push-Pull-Tab
连接器类型 B端 LCDU/APC
连接器端面 B APC 8°
连接器 A外壳颜色 绿色
Release mechanism side B Push-Pull-Tab
光纤类型 E9/125 G.652.D BLO
插芯材料 Zirconia
插入损耗(最大值)A 0.25 dB
插入损耗 (典型值)A 0.12 dB
回波损耗 (最小值)A 50 dB
回波损耗 (典型值)A 55 dB
插入损耗(最大值)B 0.25 dB
插入损耗 (典型值)B 0.12 dB
回波损耗 (最小值)B 65 dB
回波损耗 (典型值)B 75 dB