SMDC – Single-rack

up to 10 kVA, internal or outdoor condenser

Produktvarianten & Lagerbestand

Artikel-Nr. Lagerbestand ProduktÄußere Abmessungen (HxBxT)Kühlung KapazitätMaximale USV-Kapazität [kVA]IT-LastVerfügbarer PlatzCooling / CondenserInput powerGewicht [kg]GTIN / EAN
40014180ZY
SMDC 3kVA42 HE, 2000 x 800 x 1400 mm3.532.7 kW24 - 27 URack-mounted / internal220 - 240 VAC, 1Ph+N+PE 50/60 Hz480 kg40393910220995
40014190ZY
SMDC 6kVA42 HE, 2000 x 1100 x 1400 mm5.565.4 kW27 - 31 UIn-row / outdoor220~240 VAC, 1Ph+N+PE 50/60 Hz800 kg40393910221008
40014630ZY
SMDC 10kVA42 HE, 2000 x 1100 x 1400 mm12.5109 kW24 - 27 UIn-row / outdoor380 - 415 VAC, 3Ph+N+PE 50/60 Hz800 kg40393910221169

Technische Daten

The Smart Modular Data Centre (SMDC) is a scalable, pre-assembled, plug-and-play solution designed for edge computing and optimised for rapid deployment.
Each single-rack SMDC features a configurable power supply unit and a redundant cooling system, providing seamless scalability and technology upgrades with little additional cost or disruption.
This single-rack solution ensures a capacity of up to 10 kVA. It consists of a 42U rack, an integrated intelligent power distribution, an uninterruptible power supply (UPS) and a compact cooling system – either integrated up to 3.5 kW or with an in-row cooler and external condenser with a capacity of up to 12.5 kW.
It also includes a fire extinguishing system, air gap sealing and comprehensive software for infrastructure management.
The single-rack SMDC supports edge computing, operating smart facilities with IoT devices, remote or branch offices or serves as a floor distributor (FD).
Advanced applications include technologies such as AI, AR, VR and automation systems that require flexible, scalable and energy-efficient real-time data processing.
Notfall-Belüftung Top of the rack and front door, extracting hot air from the rack in case of cooling failure
Stromverteilung PDM6 input breaker, 63A/1P*1 (3 or 6 kVA) / PDM10 input breaker, 125A/3P*1 (10 kVA)
PDU Intelligent power management
USV-Kapazität up to 10 kVA
Verlängerung der Autonomiezeit der USV (optional) 10 to 15 minutes
Kühlung in rack (up to 3.5 kW), in row (up to 12.5 kW)
DCIM Real-time status monitor and control
Benutzeroberfläche 10.4" touch screen and remote web interface
Sensoren Cooling system, UPS, power usage effectiveness (PUE), iPDU*, IT load, access control*, temperature, humidity and alarm status
Alarm und Benachrichtigung Sound and light alarm with SMS and email notification
Zutrittskontrolle Card or keypad
Brandbekämpfung NOVEC 1230 rack mounted (2U)*
Fronttür mit 5 mm gehärtetem Doppelglas (gilt nicht für Reihenkühler)
Rücktür aus massivem Stahlblech
Seitenwände abnehmbar, mit Erdungsbolzen
Dachplatte Kabeleinführung möglich
Bodenplatte Kabeleinführung möglich
Befestigungsprofil 2 Paar 19-Zoll-Vertikalprofile (vorne / hinten)

Dokumentation