JE-H(St)H...Bd FE180 E30-E90 fire alarm B2ca
Fire alarm cable, max. 225V, Keram
halogen-free, with improved fire characteristics,
with reference to VDE 0815,
circuit integrity (FE180) in accordance with VDE 0472-814, IEC 60331, EN 50200,
System Circuit Integrity E30-E90* in accordance with DIN 4102-12
Fire behaviour according to EN 50575, EN 13601-6
1 Conductor: solid
2 Insulation: cross-linked polymer, zero halogen
3 Drain wire: Ø 0.8 mm
4 Separator: plastic tape, zero halogen
5 Shielding: Al-laminated tape, zero halogen
6 Sheath: FRNC/LSZH
Product variants & stock
| Article No. | Stock | Product | Reaction to fire | Number of cores | Outer sheath diameter [mm] | CU rate [kg/km] | Weight [kg/km] | Fire load [kWh/m] | Packing unit | GTIN / EAN |
|---|---|---|---|---|---|---|---|---|---|---|
| 18809300BL | JE-H(St)H...Bd FE180 E30-E90 fire alarm 1x2x0.8 mm | B2ca-s1a,d1,a1 | 2 | 5.6 | 15 | 40.3 | 0.108 | 500 m drum | 40393910474091 | |
| 18809300BK | JE-H(St)H...Bd FE180 E30-E90 fire alarm 1x2x0.8 mm | B2ca-s1a,d1,a1 | 2 | 5.6 | 15 | 40.3 | 0.108 | 1000 m drum | 40393910474077 | |
| 18809300BZ | JE-H(St)H...Bd FE180 E30-E90 fire alarm 1x2x0.8 mm | B2ca-s1a,d1,a1 | 2 | 5.6 | 15 | 40.3 | 0.108 | by the metre | 40393910230277 | |
| 18809800BL | JE-H(St)H...Bd FE180 E30-E90 fire alarm 2x2x0.8 mm | B2ca-s1a,d1,a1 | 2 | 6.3 | 25 | 58.8 | 0.138 | 500 m drum | 40393910474190 | |
| 18809800BK | JE-H(St)H...Bd FE180 E30-E90 fire alarm 2x2x0.8 mm | B2ca-s1a,d1,a1 | 2 | 6.3 | 25 | 58.8 | 0.138 | 1000 m drum | 40393910474176 | |
| 18809800BZ | JE-H(St)H...Bd FE180 E30-E90 fire alarm 2x2x0.8 mm | B2ca-s1a,d1,a1 | 2 | 6.3 | 25 | 58.8 | 0.138 | by the metre | 40393910230291 | |
| 18810100BZ | JE-H(St)H...Bd FE180 E30-E90 fire alarm 4x2x0.8 mm | B2ca-s1a,d1,a1 | 2 | 9.0 | 45 | 100.5 | 0.224 | by the metre | 40393910230314 | |
| 18810300BZ | JE-H(St)H...Bd FE180 E30-E90 fire alarm 8x2x0.8 mm | B2ca-s1a,d1,a1 | 2 | 13.9 | 85 | 223.9 | 0.522 | by the metre | 40393910230338 | |
| 18810500BZ | JE-H(St)H...Bd FE180 E30-E90 fire alarm 12x2x0.8 mm | B2ca-s1a,d1,a1 | 2 | 14.8 | 126 | 285.3 | 0.605 | by the metre | 40393910230352 | |
| 18810700BZ | JE-H(St)H...Bd FE180 E30-E90 fire alarm 16x2x0.8 mm | B2ca-s1a,d1,a1 | 2 | 16.6 | 166 | 331.1 | 0.628 | by the metre | 40393910230376 | |
| 18810900BZ | JE-H(St)H...Bd FE180 E30-E90 fire alarm 20x2x0.8 mm | B2ca-s1a,d1,a1 | 2 | 18.8 | 206 | 428.4 | 0.842 | by the metre | 40393910230390 |
Technical specifications
Permitted operating temperature at conductor of +70˚C.
Suitable according to VKF fire protection guideline in escape routes and in tunnels according to Astra guideline 13022.
| operating capacity, 1km @ 800Hz | 120 |
|---|---|
| Test voltage 50Hz, core/core | 500 |
| peak voltage | 225 |
| Capacitive coupling 0,8 mm, 100m @ 800Hz | 200 |
| Maximum loop resistance 0,8 mm | 73.2 |
| Minimum insulation resistance | 100 |
| Test voltage 50Hz, core/screen | 2000 |
| Circuit integrity | FE 180 |
|---|---|
| System circuit integrity | E90 |
| Installation temperature | -5 °C - +50 °C |
| Operating temperature | -30 °C - +70 °C |
| System Circuit Integrity is dependent on installation method. |
| Conductor | Bare copper, solid, 0.8 mm diameter, VDE 0815 |
|---|---|
| Insulation | Fire-resistant, cross-linked, high-performance Keram special compound, EN 50290-2-36 |
| Core colours | VDE 0815 |
| Shielding | Al-laminated tape with copper drain wire Ø 0.8 mm |
| Outer sheath material | Flame retardant polyolefin compound VDE 0819-107, EN 50290-2-27 and VDE 0250-214 "HM 2" |
| Outer sheath colour | red |
| Circuit integrity | IEC 60331-11/-21 (180 minutes), VDE 0472-814 (FE180), IEC 60331-1 (120 minutes), IEC 60331-2 (120 minutes), EN 50200 (PH120 minutes), NBN 713-020 (Rf 1 1/2), VDE 0482-200 (PH120), AREI-RGIE Section 4.3.3 FR1 |
|---|---|
| System circuit integrity | DIN 4102-12, AREI-RGIE Section 4.3.3 FR2 |
| Reaction to fire | EN 13501-6 |
| Euroclass | B2ca |
| Smoke density | IEC 61034-1/-2, EN 61034-1/-2, VDE 0482-1034-1/-2, AREI-RGIE Section 4.3.3 SD |
| Zero halogen no corrosive gases | IEC 60754-1/-2, EN 60754-1/-2, VDE 0482-754-1/-2, AREI-RGIE Section 4.3.3 SA |
| Flame propagation | IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-1-2, AREI-RGIE Section 4.3.3 F1 |
| Flame spread | IEC 60332-3-22/-24, EN 60332-3-22/-24, VDE 0482-332-3-22/-24, AREI-RGIE Section 4.3.3 F2 |
| Minimum bending during installation (multi core) | 7.5 x D |
|---|---|
| Minimum bending radius permanent (multi core) | 7.5 x D |
| Minimal crush resistance / 10cm | 1000 N |
Documentation
-
VDE Certificate
Download PDF [ 341.093 KB ]
-
VDE Certificate
Download PDF [ 158.254 KB ]
-
Datasheet
Download PDF [ 122.302 KB ]
-
Datasheet
Download PDF [ 121.168 KB ]
-
Datasheet
Download PDF [ 123.33 KB ]
-
Datasheet
Download PDF [ 122.275 KB ]
-
Datasheet
Download PDF [ 122.66 KB ]
-
Datasheet
Download PDF [ 121.493 KB ]
-
MPA Certificate
Download PDF [ 3.409 MB ]